331
Motor
Disjuntor
Contator
Relé térmico
Teste
Potência
nominal
(kW)*
Corrente
Nominal
(A)
Tipo
Corrente
Nominal
(A)
Limiar
Magnético
(A)
Ref.
Tipo
Tipo
Faixa de
ajuste
(A)
Ref.
Corrente
condicional de
curto-circuito
Iq(kA)
Tensão
(V)
0.75
1.9
DX-MA
2.5
32
071 62
CTX-1 9 A
RTX-1
1.8 - 2.7
294 61
15
400
1.1
2.7
DX-MA
4
50
071 63
CTX-1 9 A
RTX-1
2.5 - 4
294 62
15
400
1.5
3.5
DX-MA
4
50
071 63
CTX-1 9 A
RTX-1
2.5 - 4
294 62
15
400
2.2
5
DX-MA
6.3
80
071 64
CTX-1 9 A
RTX-1
4 - 6.3
294 63
15
400
2.5
5.7
DX-MA
6.3
80
071 64
CTX-1 9 A
RTX-1
4 - 6.3
294 63
15
400
3
6.7
DX-MA
10
125
071 52
CTX-1 12 A
RTX-1
5.5 - 8.5
294 64
15
400
3.7
8
DX-MA
10
125
071 52
CTX-1 12 A
RTX-1
5.5 - 8.5
294 64
15
400
4
8.5
DX-MA
10
125
071 52
CTX-1 12 A
RTX-1
8 - 12
294 65
15
400
5.5
11
DX-MA
12.5
160
071 53
CTX-1 25 A
RTX-1
8 - 12
294 65
15
400
6.3
13
DX-MA
16
200
071 54
CTX-1 25 A
RTX-1
10 - 16
294 66
15
400
7.5
15
DX-MA
16
200
071 54
CTX-1 25 A
RTX-1
10 - 16
294 66
15
400
10
20
DX-MA
25
320
071 55
CTX-1 25 A
RTX-1
17.5 - 22
294 68
15
400
11
22
DX-MA
25
320
071 55
CTX-1 25 A
RTX-1
17.5 - 22
294 68
15
400
12.5
25
DX-MA
25
320
071 55
CTX-1 25 A
RTX-1
21 - 26
294 69
15
400
15
29
DX-MA
40
500
071 56
CTX-1 32 A
RTX-1
25 - 32
294 70
10
400
16
31
DX-MA
40
500
071 56
CTX-1 32 A
RTX-1
25 - 32
294 70
10
400
18.5
35
DX-MA
40
500
071 56
CTX-1 40 A
RTX-1
30 - 40
294 71
10
400
20
38
DX-MA
40
500
071 56
CTX-1 40 A
RTX-1
30 - 40
294 71
10
400
22
41
DX-MA
63
880
071 60
CTX-1 50 A
RTX-1
30 - 43
294 73
10
400
25
47
DX-MA
63
880
071 60
CTX-1 50 A
RTX-1
42 - 55
294 74
10
400
30
57
DX-MA
63
880
071 60
CTX-1 65 A
RTX-1
54 - 65
294 75
10
400
31.5
59
DX-MA
63
880
071 60
CTX-1 65 A
RTX-1
54 - 65
294 75
10
400
Motor
Disjuntor
Contator
Relé térmico
Teste
Potência
nominal
(kW)*
Corrente
Nominal
(A)
Tipo
Corrente
Nominal
(A)
Limiar
Magnético
(A)
Ref.
Tipo
Tipo
Faixa de
ajuste
(A)
Ref.
Corrente
condicional de
curto-circuito
Iq(kA)
Tensão
(V)
12.5
25
DPX-H 125
25
250
250 51
CTX-1 50 A
RTX-1
24 - 32
294 72
36
400
15
29
DPX-H 125
40
400
250 52
CTX-1 95 A
RTX-1
24 - 32
294 72
36
400
16
31
DPX-H 125
40
400
250 52
CTX-1 95 A
RTX-1
24 - 32
294 72
36
400
18.5
35
DPX-H 125
40
400
250 52
CTX-1 95 A
RTX-1
30 - 43
294 73
36
400
20
38
DPX-H 125
40
400
250 52
CTX-1 95 A
RTX-1
30 - 43
294 73
36
400
22
41
DPX-H 125
63
630
250 53
CTX-1 95 A
RTX-1
30 - 43
294 73
36
400
25
47
DPX-H 125
63
630
250 53
CTX-1 95 A
RTX-1
42 - 55
294 74
36
400
30
57
DPX-H 125
63
630
250 53
CTX-1 105 A RTX-1
54 - 65
294 75
36
400
31.5
59
DPX-H 125
63
630
250 53
CTX-1 105 A RTX-1
54 - 65
294 75
36
400
37
68
DPX-H 125
100
1000
250 54
CTX-1 105 A RTX-1
64 - 82
294 76
36
400
40
74
DPX-H 125
100
1000
250 54
CTX-1 105 A RTX-1
64 - 82
294 76
36
400
45
82
DPX-H 125
100
1000
250 54
CTX-1 105 A RTX-1
78 - 97
294 77
36
400
50
92
DPX-H 125
100
1000
250 54
CTX-1 105 A RTX-1
78 - 97
294 77
36
400
55
102
DPX-H 125
125
1250
250 55
CTX-2 150 A RTX-2
90 - 120
294 83
36
400
63
115
DPX-H 125
125
1250
250 55
CTX-2 150 A RTX-2
90 - 120
294 83
36
400
■
Coordenação dos contatores/disjuntores
De acordo com IEC 60947-2
Coordenação tipo 2
Combinação tripolar
* para obter o valor da potência nominal em (CV) dividir por 0,736
Contatores CTX-1 e CTX-2