Catalogo_Legrand - page 117

115
Limites de seletividade (valores médios kA em 400 V
±
)
Disjuntores caixa moldada
à jusante
In
Disjuntores caixa aberta à montante
DMX
3
- N 2500
(50 kA)
DMX
3
- H 2500
(65 kA)
DMX
3
- L 2500
(100 kA)
DMX
3
-N
4000
(50 kA)
DMX
3
-H
4000
(65 kA)
DMX
3
-L
4000
(100 kA)
800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500 800 1000 1250 1600 2000 2500 3200 4000 3200 4000 3200 4000
DPX
3
160
(16, 25, 36, 50 kA)
com ou sem módulo de fuga
à terra
16 T T T T T T T T T T T T T T T T T T T T T T T T
25 T T T T T T T T T T T T T T T T T T T T T T T T
40 T T T T T T T T T T T T T T T T T T T T T T T T
63 T T T T T T T T T T T T T T T T T T T T T T T T
80 T T T T T T T T T T T T T T T T T T T T T T T T
100 T T T T T T T T T T T T T T T T T T T T T T T T
125 T T T T T T T T T T T T T T T T T T T T T T T T
160 T T T T T 88 T T T T T T T T T T T T T T T T T T
DPX
3
250 termomagnético
(25, 36, 50 kA)
com ou sem módulo de fuga
à terra
100 T T T T T T T T T T T T T T T T T T T T T T T T
160 T T T T T T T T T T T T T T T T T T T T T T T T
200 T T T T T T T T T T T T T T T T T T T T T T T T
250 T T T T T T T T T T T T T T T T T T T T T T T T
DPX
3
250 termomagnético
(70 kA)
com ou sem módulo de fuga
à terra
100 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
160 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
200 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
250 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
DPX
3
250 eletrônico
(1)
(25, 36, 50 kA)
com ou sem módulo de fuga
à terra
40 T T T T T T T T T T T T T T T T T T T T T T T T
100 T T T T T T T T T T T T T T T T T T T T T T T T
160 T T T T T T T T T T T T T T T T T T T T T T T T
200 T T T T T T T T T T T T T T T T T T T T T T T T
250 T T T T T T T T T T T T T T T T T T T T T T T T
DPX
3
250 eletrônico
(1)
(70 kA)
com ou sem módulo de fuga
à terra
40 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
100 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
160 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
200 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
250 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
DPX
3
250 eletrônico
(2)
(25, 36, 50 kA)
com ou sem módulo de fuga
à terra
40 T T T T T T T T T T T T T T T T T T T T T T T T
100 T T T T T T T T T T T T T T T T T T T T T T T T
160 T T T T T T T T T T T T T T T T T T T T T T T T
200 T T T T T T T T T T T T T T T T T T T T T T T T
250 T T T T T T T T T T T T T T T T T T T T T T T T
DPX
3
250 eletrônico
(2)
(70 kA)
com ou sem módulo de fuga
à terra
40 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
100 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
160 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
200 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
250 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
DPX
3
630
termomagnético
(36 kA)
250 T T T T T T T T T T T T T T T T T T T T T T T T
320 T T T T T T T T T T T T T T T T T T T T T T T T
400 T T T T T T T T T T T T T T T T T T T T T T T T
500 T T T T T T T T T T T T T T T T T T T T T T T T
630 -
T T T T T -
T T T T T -
T T T T T T T T T T T
DPX
3
-H 630
termomagnético
(70 kA)
250 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
320 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
400 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
500 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
630 -
-
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T
DPX
3
eletrônico
(1)
S1 e S2 (36 kA)
250 T T T T T T T T T T T T T T T T T T T T T T T T
400 T T T T T T T T T T T T T T T T T T T T T T T T
630 -
T T T T T -
T T T T T -
T T T T T T T T T T T
DPX
3
eletrônico
(2)
S1 e S2 (36 kA)
250 T T T T T T T T T T T T T T T T T T T T T T T T
400 T T T T T T T T T T T T T T T T T T T T T T T T
630 -
T T T T T -
T T T T T -
T T T T T T T T T T T
DPX
3
-H 630
eletrônico
(1)
S1 e S2 (70 kA)
250 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
400 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
630 -
-
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T
DPX
3
-H 630
eletrônico
(2)
S1 e S2 (70 kA)
250 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
400 -
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T T
630 -
-
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T T
DPX
3
termomagnético
(50 kA)
800 -
-
T T T T -
-
T T T T -
-
T T T T T T T T T T
1000 -
-
-
T T T -
-
-
T T T -
-
-
T T T T T T T T T
1250 -
-
-
-
T T -
-
-
-
T T -
-
-
-
T T T T T T T T
DPX
3
-H 1250
termomagnético
(70 kA)
800 -
-
-
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T T
1000 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T T
1250 -
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
T T T T T T T T
DPX
3
e DPX
3
-H 1600
eletrônico
(1)
S1 e S2
(50, 70 kA)
800 -
-
T T T T -
-
T T T T -
-
T T T T T T T T T T
1250 -
-
-
-
T T -
-
-
-
T T -
-
-
T T T T T T T T T
1600 -
-
-
-
-
T -
-
-
-
T T -
-
-
-
T T T T T T T T
DPX
3
e DPX
3
-H 1600
eletrônico
(2)
S1 e S2
(50, 70 kA)
800 -
-
T T T T -
-
T T T T -
-
T T T T T T T T T T
1250 -
-
-
-
T T -
-
-
-
T T -
-
-
T T T T T T T T T
1600 -
-
-
-
-
T -
-
-
-
T T -
-
-
-
T T T T T T T T
T = seletividade total, até a capacidade de interrupção do disjuntor à jusante de acordo com a norma IEC 60947-2
(1) Relé eletrônico, chave seletora em "HIGH" - (2) Relé eletrônico, chave seletora em "LOW"
Tabela de seletividade DMX
3
/ DPX
3
1...,107,108,109,110,111,112,113,114,115,116 118,119,120,121,122,123,124,125,126,127,...828